Using Monte Carlo Simulation to Calculate The Dose Reduction at The Maze Entrance of A Radiotherapy Room

Main Article Content

Dindar Sh. Bari

Abstract

The aim of this study was to introduce a method to reduce the dose of the backscattered photons from a linear accelerator at the maze entrance of a radiotherapy room (RR). For this purpose a typical RR was designed and simulated using FLUKA Monte Carlo Code (version 2011.2b.1). The maze of a RR was the main focus for the study. Its walls including, floor and ceiling were lined with thin sheets of lead and stainless steel of 2 mm and 4 mm thicknesses respectively to find the most effective material and thickness for dose reducing. It was found that 2 mm lead sheet was able to reduce the dose at the maze entrance by more than 60 % and 4 mm 70 %. Whereas, 2 mm of stainless steel was able to reduce about 30% of the dose and 4 mm was able to reduce about 35%.

Downloads

Download data is not yet available.

Article Details

Section

Science Journal of University of Zakho

Author Biography

Dindar Sh. Bari, University of Zakho

Department of Physics, Faculty of Science, University of Zakho, Kurdistan Region – Iraq.

How to Cite

Bari, D. S. (2014). Using Monte Carlo Simulation to Calculate The Dose Reduction at The Maze Entrance of A Radiotherapy Room. Science Journal of University of Zakho, 2(2), 375-381. https://stest.uoz.edu.krd/index.php/sjuoz/article/view/258